IKON Group
Mechanical Utilities

Chillers & Vapour Absorption Machines

Lithium Bromide (LiBr) Absorption Chillers

IKON Group supplies, commissions, and maintains high-performance industrial Vapour Absorption Machines (VAM). By utilizing the thermodynamic affinity between Lithium Bromide (as the absorbent) and Water (as the refrigerant) in a high-vacuum chamber, these machines bypass heavy electrical compression demands entirely.

Our absorption units run directly on steam, hot water, exhaust gases, or natural gas. This makes them highly competitive in process plants containing abundant waste heat or in regions where commercial electricity prices are expensive.

SYSTEM CONFIGURATIONS
  • Single-Effect VAM: Driven by low-pressure steam or hot water, optimizing fuel costs in basic processes.
  • Double-Effect VAM: Series-flow solution design featuring high and low pressure generators, achieving over 50% higher thermal efficiency.
  • Direct-Fired absorption: Configured to combust natural gas, light fuel oil, or diesel directly inside primary generator zones.
Technical Specs

Absorption System Parameters

IKON Group maintains precise operating standards for our absorption installations to ensure continuous process cycles.

System ParameterSingle-Effect CycleDouble-Effect CycleDirect-Fired Series
Refrigerant Loop FluidPristine Water (H₂O)Pristine Water (H₂O)Pristine Water (H₂O)
Absorbent Liquid LoopLithium Bromide (LiBr)Lithium Bromide (LiBr)Lithium Bromide (LiBr)
Energy Heat SourceLow-Pressure Steam (0.1 MPa) / Hot WaterMedium-Pressure Steam (0.8 MPa)Natural Gas / Light Diesel Oil
Average Thermal COP0.70 - 0.751.20 - 1.351.15 - 1.25
Chilled Water Outlets7°C (standard)5°C - 7°C6°C - 7°C
Electricity ReductionSaves up to 80% grid powerSaves up to 75% grid powerSaves up to 78% grid power
System Advantages

Why Install Vapour Absorption Machinery?

Thermal Energy Recovery

Utilizes waste jacket water, exhaust turbine steam, or flue gases, converting waste heat into high-capacity refrigeration.

Drastic Grid Power Savings

With only low-wattage solution pumps operating, absorption machinery reduces peak electrical utility draw by up to 80%.

Mechanical Simplicity

Since there are no heavy dynamic compressors or moving mechanical shafts under vacuum, vibration and wear are minimal.

Need Emergency Temporary Cooling or a Technical Plant Audit?

IKON Group coordinates chiller shipments within hours. Contact our sales presence across India, Bangladesh & Sri Lanka to arrange diagnostic support or immediate modular rental chillers.